Rexroth IndraDrive Electromagnetic Compatibility (EMC) 8-13
DOK-INDRV*-SYSTEM*****-PR02-EN-P
Mains Filters for Drive Controllers HCS03
Note: At HCS03.1E drive controllers, do not operate any external
additional capacitances at the DC bus.
Exception: For drive controllers HCS03.1E-...-W0210 this is
allowed.
Limit Value Classes for HCS03 Drive Controllers with
HNK01
Drive controller
type
Mains filter type Max.
allowed
number of
drive contr.
or axes
Max. allowed
total length
of motor
cable
[ m ]
PWM
frequ.
[kHz]
Allowed leakage capacitance
to comply with limit value
class
[ nF ]
HCS03 A2.1 A2.2 A1 B1
HCS03.1E-W0070 HNK01.1A-A075-E0050 1 75
4
8
12
16
tbd tbd tbd tbd
HCS03.1E-W0100 HNK01.1A-A075-E0080 1 75
4
8
12
16
tbd tbd tbd tbd
HCS03.1E-W0150 HNK01.1A-A075-E0106 1 75
4
8
12
16
tbd tbd tbd tbd
HCS03.1E-W0210 HNK01.1A-A075-E0146 1 75
4
8
12
16
tbd tbd tbd tbd
tbd in preparation
Fig. 8-9: Supply modules HMV with mains filter HNK