140 Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
Chapter 6 Configure and Start Up the Kinetix 6000 Drive System
14. From the Bus Regulator Catalog Number pull-down menu, choose the
shunt option appropriate for your actual hardware configuration.
15. Click OK.
16. Repeat step 1
…step 10 for each Bulletin 2094 AM module.
If your IAM module is
And your hardware configuration includes this shunt
option
Then choose
Configured as an IAM module or
common-bus leader IAM module
(1)
Internal shunt resistors only Internal or <none>
Bulletin 2094 (rail mounted) shunt module 2094-BSP2
Bulletin 1394 passive shunt module (connected to the
2094-BSP2 shunt module)
1394-SRxxxx
Bulletin 1336 active shunt module Internal or <none>
Configured as a common-bus follower IAM module
(2)
N/A. Shunts are disabled on follower IAM module CommonBus Follow
(1) Drive will not accept Internal, <none>, 2094-BSP2, or 1394-SRxxxx selection if DC bus voltage is present without having three-phase power applied.
(2) Drive will not accept CommonBus Follow selection if three-phase power or DC bus power is applied.
To avoid damage to your Bulletin 1394 external shunt module when wired to
the 2094-BSP2 shunt module, verify that the proper 230V or 460V fuse is
installed prior to applying power.
Refer to External Shunt Module Specifications on page 194
, for more
information.
When configured to use the Bulletin 1394 or 2094 shunt modules, the
IAM bus regulator capacity attribute displays the utilization of total shunt
power available (as a percent) based on the power rail configuration.
Refer to External Shunt Module Specifications on page 194
for shunt
power specification and examples.
DC common-bus applications must calculate Total Bus Capacitance and
Additional Bus Capacitance and set the Add Bus Cap parameter in the
leader IAM module by using DriveExplorer or RSLogix 5000 software.
Refer to Appendix D beginning on page 245
, for more information on
making the calculations. Refer to Appendix E beginning on page 253
, for
more information on setting the Add Bus Cap parameter.