Rockwell Automation Publication 2094-UM001D-EN-P - May 2010 181
Specifications and Dimensions Appendix A
Table 97 - IAM Module (460V) Power Specifications (series A and B)
Attribute 2094-BC01-MP5-x 2094-BC01-M01-x 2094-BC02-M02-x 2094-BC04-M03-x 2094-BC07-M05-x
AC input voltage 324…528V rms
three-phase (360…480V nom)
AC input frequency 47…63 Hz
Main AC input current
Nom (rms)
Max inrush (0-pk)
(1)
10.0 A
11.0 A
24.0 A
22.0 A
44.0 A
31.1 A
71.0 A
62.2 A
DC input voltage (common bus follower) 458…747V DC
DC input current
(common-bus follower) 9.0 A 22.6 A 41.5 A 67.7 A
Control power AC input voltage
95…264V rms
single-phase (110…240V rms nom)
Control power AC input current
Nom (@ 220/230V AC) rms
Nom (@ 110/115V AC) rms
Max inrush (0-pk)
3 A
6 A
98 A
(2)
Nominal bus output voltage 650V DC
Line loss ride through 20 ms
Continuous output current to bus (A
dc
)
9.0 A 22.6 A 41.5 A 67.7 A
Peak output current to bus (A
dc
)
Series A drives
(3)
Series B drives
18.1 A
22.6 A
(4)
45.2 A
56.4 A
(4)
83.1 A
103.8 A
(4)
135.4 A
203.2 A
(5)
Bus overvoltage 825V DC
Bus undervoltage 275V DC (when enabled) 425V DC (at the completion of pre-charge)
Internal shunt
Continuous power
Peak power
50 W
5.6 kW
200 W
22.5 kW
Internal shunt resistor 115 Ω 28.75 Ω
Shunt on 805V DC
Shunt off 755V DC
Continuous power output to bus 6 kW 15 kW 27.6 kW 45 kW
Peak power output at 480V
Series A drives
(3)
Series B drives
12 kW
15 kW
(4)
30 kW
37 kW
(4)
55.2 kW
69 kW
(4)
90 kW
135 kW
(5)
Efficiency 97%
Converter inductance 500 μH125 μH75 μH
Converter capacitance 110 μF220 μF940 μF 1410 μF
Short circuit current rating 200,000 A (rms) symmetrical
(1) All IAM modules are limited to 2 contactor cycles per minute (with up to 4 axes), or 1 contactor cycle per minute (with 5…8 axes). The cycle capability also depends on the
converter power rating and the total system capacitance. Refer to Input Power Cycle Capability on page 68
, when making calculations.
(2) For eight axis systems with 230V AC control input voltage and 50 °C (122 °F) ambient temperature the maximum inrush duration is less than 1/2 line cycle. To calculate the
maximum inrush duration for other configurations, refer to Refer to Control Power on page 72
, when making calculations.
(3) Peak output current duration equals 250 ms.
(4) Converter peak output duration equals 400 ms with a duty cycle of 16%.
(5) Converter peak output duration equals 200 ms with a duty cycle of 3%.