Date Code 20010719 701 Motor Protection Relay
Event Analysis
Sequential Events Recorder (SER) Report
9.15
The date entries in the previous example SER commands depend on the Date
Format setting DATE_F. If setting DATE_F is equal to MDY, you should enter the
dates as in the above examples (Month/Day/Year). If setting DATE_F is equal to YMD,
you should enter the dates Year/Month/Day. If the requested SER event report rows do
not exist, the relay responds No SER Data.
Resetting the SER Report Buffer
Reset the SER data with the serial port SER R command.