F.24
SEL-734 Meter Instruction Manual Date Code 20090730
Modbus RTU Communications Protocol
Modbus RTU Communications Protocol
12424–12425 3088–3089 Rate A Max MVARTotal Peak Demand LONG
1242612427 308A–308B PF at Rate A Max MVAR Total Peak Demand LONG100
12428–12429 308C–308D Rate A Max MVA “Total Peak Demand LONG
1243012431 308E–308F PF at Rate A Max MVA “Total Peak Demand LONG100
12432–12433 3090–3091 Rate B Max MWTotal Peak Demand LONG
1243412435 30923093 PF at Rate B Max MW Total Peak Demand LONG100
12436–12437 3094–3095 Rate B Max MVARTotal” Peak Demand LONG
1243812439 30963097 PF at Rate B Max MVARTotal Peak Demand LONG100
12440–12441 3098–3099 Rate B Max MVA “Total Peak Demand LONG
1244212443 309A–309B PF at Rate B Max MVA Total Peak Demand LONG100
12444–12445 309C–309D Rate C Max MWTotal Peak Demand LONG
1244612447 309E–309F PF at Rate C Max MW Total Peak Demand LONG100
12448–12449 30A0–30A1 Rate C Max MVARTotal” Peak Demand LONG
1245012451 30A230A3 PF at Rate C Max MVARTotal Peak Demand LONG100
12452–12453 30A4–30A5 Rate C Max MVA “Total Peak Demand LONG
1245412455 30A630A7 PF at Rate C Max MVA Total Peak Demand LONG100
12456–12457 30A8–30A9 Rate D Max MW “Total Peak Demand LONG
1245812459 30AA–30AB PF at Rate D Max MW Total Peak Demand LONG100
12460–12461 30AC–30AD Rate D Max MVARTotal Peak Demand LONG
1246212461 30AE–30AF PF at Rate D Max MVAR Total Peak Demand LONG100
12464–12465 30B0–30B1 Rate D Max MVA “Total Peak Demand LONG
1246612467 30B230B3 PF at Rate D Max MVA “Total Peak Demand LONG100
12468–12469 30B4–30B5 Rate E Max MWTotal Peak Demand LONG
1247012471 30B630B7 PF at Rate E Max MW Total Peak Demand LONG100
12472–12473 30B8–30B9 Rate E Max MVAR Total” Peak Demand LONG
1247412475 30BA–30BB PF at Rate E Max MVARTotal Peak Demand LONG100
12476–12477 30BC–30BD Rate E Max MVA “Total Peak Demand LONG
1247812479 30BE–30BF PF at Rate E Max MVA Total Peak Demand LONG100
12480–12481 30C0–30C1 Rate F Max MW Total” Peak Demand LONG
1248212483 30C230C3 PF at Rate F Max MWTotal Peak Demand LONG100
12484–12485 30C4–30C5 Rate F Max MVAR Total” Peak Demand LONG
1248612487 30C630C7 PF at Rate F Max MVAR “Total Peak Demand LONG100
12488–12489 30C8–30C9 Rate F Max MVATotal Peak Demand LONG
1249012491 30CA–30CB PF at Rate F Max MVA Total Peak Demand LONG100
12492–12509 30CC–30DD 1st Max MW, MVAR, MVA Total Peak Demand Time and Date UINT
12510–12527 30DE–30EF 2nd Max MW, MVAR, MVA Total Peak Demand Time and Date UINT
12528–12545 30F0–3101 3rd Max MW, MVAR, MVA Total Peak Demand Time and Date UINT
12546–12563 3102–3113 4th Max MW, MVAR, MVA Total Peak Demand Time and Date UINT
12564–12581 3114–3125 5th Max MW, MVAR, MVA Total Peak Demand Time and Date UINT
12582–12599 3126–3137 Rate A Max MW, MVAR, MVA Total Peak Demand Time and Date UINT
12600–12617 3138–3149 Rate B Max MW, MVAR, MVA Total Peak Demand Time and Date UINT
Table F.23 Modbus Register Map (Sheet 14 of 19)
Address Field Notes Min Max Conversion
Courtesy of NationalSwitchgear.com