Name Use Data type Definition Values Safety implica‐
t
ion
SafeCutOffPath02
…
S
afeCutOffPath08
Safety function BOOL Cut-off path 02 … 08
(safety-oriented)
The signal is ON, if all
of the following criteria
are met:
1)
•
The currently moni‐
tored field in the
cut-off path is
safety-oriented
•
The currently moni‐
tored field in the
cut-off path is free
•
The restart interlock
was not triggered
0 = OFF state,
protective field
interrupted
Safety-relevant
parameter
1 = ON state,
pr
otective field
free
StandbymodeActive Diagnostics BOOL Status sleep mode
Signals whether the
device is in sleep
mode.
0 = device not in
sleep mode
Parameter with‐
out safety impli‐
cation
1 = device in
sleep mode
StatusSafeCutOffPath01 Additional func‐
tion
BOOL Status of the safety-
related cut-off path 01
(Not safety-related)
Signals the status
of the relevant safety-
related cut-off path.
0 = safety-
related cut-off
path in OFF state
Parameter with‐
out safety impli‐
cation
1 = safety-
r
elated cut-off
path in ON state
StatusSafeCutOffPath02
…
St
atusSafeCutOffPath08
Additional func‐
tion
BOOL Status of the safety-
related cut-off path
02 … 08 (Not safety-
related)
Signals the status
of the relevant safety-
related cut-off path.
1)
0 = safety-
related cut-off
path in OFF state
Parameter with‐
out safety impli‐
cation
1 = safety-
related cut-off
path in ON state
1)
Cut-off paths 5 to 8 are only available for the Pro performance package.
13.6.1.2 Content of the process images
13.6.1.2.1 Process image, length 12 bytes
Table 51: Safety-related PROFIsafe process image: input of the device, output of the control
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Reserved ActivateS‐
t
andbyMode
StopAlarm‐
Detection
Reserved TriggerRun‐
Mode
1 SetMonitoringCaseNoTable1
2 SetMonitoringCaseNoTable2
3 SetMonitoringCaseNoTable3
4 SetMonitoringCaseNoTable4
5 Reserved
6 Reserved
7 Reserved
8 Reserved
9
1)
TriggerReset‐
CutOf
f‐
Path08
TriggerReset‐
CutOff‐
Path07
TriggerReset‐
CutOff‐
Path06
TriggerReset‐
CutOff‐
Path05
TriggerReset‐
CutOff‐
Path04
TriggerReset‐
CutOff‐
Path03
TriggerReset‐
CutOff‐
Path02
TriggerReset‐
CutOff‐
Path01
13 TECHNICAL DATA