Released: A teach-in process can be triggered using the button.
Locked: The teach-in button is locked to prevent inadvertent actuation, for exam‐
ple.
7.3.2 System settings for the EXPERT user level
I/O configuration
You can configure the inputs or outputs according to the type of MLG-2.
Figure 63: I/O configuration
The table shows the inputs and outputs, the relevant pins on the connection and the
current configuration.
The following configuration options are available:
Output, the connection is configured as an output
Input, the connection is configured as an input
Not defined, the connection has not been activated (either as an input or an output)
NOTE
If you change the configuration of a connection, all of the functions that have been con‐
figured for the input (e.g., as teach-in) or the output (e.g., for object recognition) will be
lost.
Beam numbering
On delivery, beam 1 is located on the connection side of the MLG-2. You can choose to
configure the MLG-2 so that the beam numbering begins at the top.
Figure 64: Beam numbering
This might be a good idea, for example, if you mount the MLG-2 with the connections
facing upward, but still want to measure height classification from the bottom.
CONFIGURATION WITH SOPAS ET
7
8017460.ZIK1/2017-02-13 | SICK O P E R A T I N G I N S T R U C T I O N S | MLG-2 Pro
65