During the teach-in process, the switching thresholds for all beams are individually
adjusted for the sensing range and the ambient conditions.
A teach-in process must be carried out when commissioning, when changing operating
mode or performance options, and at regular intervals in general.
7.4.1.2 Teach-in result
Table 77: Teach-in result
Index Access Data type Description
41h R UINT-8 This parameter is used to read the result of the
last teach-in.
The teach-in result is stored in 8bit:
Table 78: Teach-in result – Stored in 8bit
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Warning:
no auto‐
matic
teach-in
possible
Error:
occurred
when
blanking
beams
during
teach-in
Warning:
high-
speed
scan not
possible
Error:
occurred
with
cross-
beam
function
during
teach-in
Warning:
beam sig‐
nal
strength
too high
Warning:
beam sig‐
nal
strength
too low
Error:
occurred
with paral‐
lel-beam
function
during
teach-in
Error:
general
error
occurred
during
teach-in
7.4.1.3 Teach-in required
Table 79: Teach-in required
Index Access Data type Description
42h R BOOL This parameter is used to read whether a
teach-in is required.
0 = no teach-in required
1 = teach-in required
7.4.1.4 Teach-in with blanking
Table 80: Teach-in with blanking
Index Access Data type Description
43h R/W BOOL This parameter activates beam blanking for
each teach-in.
0 = no blanking
1 = with blanking
To show the blanked beams again, proceed as follows:
1. Remove all objects from the detection area.
2. Activate the Blank blocked beams function.
3. Activate the Teach-in with blanking function.
4. Perform a teach-in.
THE MLG-2 ON THE PROFIBUS NETWORK 7