EasyManuals Logo

Siemens siprotec 7SA6 User Manual

Siemens siprotec 7SA6
792 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #212 background imageLoading...
Page #212 background image
Functions
6-30 7SA6 Manual
C53000-G1176-C133-1
Figure 6-17 Logic of the earth fault recognition
Earth Fault
Recognition during
Single-Pole Open
Condition
The earth fault recognition is modified during the single-pole open condition with
single-pole automatic reclosure in an earthed system (Figure 6-18). In this case, the
magnitudes of the currents and voltages are monitored in addition to the angles
between the currents.
Figure 6-18 Earth fault recognition during single-pole open condition
Earth Fault
Detection
for Non-Earthed
Systems
In non-earthed systems (isolated system star point or resonant-earthed by means of
a Peterson coil) the measured displacement voltage is not used for fault detection.
Furthermore, in these systems a simple earth fault is assumed initially in case of a sin-
gle-phase fault and the fault detection is suppressed in order to avoid an erroneous
pickup as a result of the earth fault initiation transients. After a time delay 7,
3+$6,which can be set, the fault detection is released again; this is necessary for
the distance protection to still be able to detect a double earth fault with one base point
on a dead-end feeder.
If, however, an earth fault is already present in the system, it is detected by the
displacement voltage detection (8!&203,62/). In this case, there is no delay
time: an earth fault now occurring in a different phase can only be due to a double
earth fault. If, apart from the displacement measurement (8!&203,62/), there
is a fault detection in more than one phase, this is also rated as a double earth fault.
In this way, double earth faults can be detected even if no or only little earth current
flows via the measuring point.
3I
0
3I
2 3I
2
1
3U
0
3I
0
I
Ph
3I
0
3V0>
I
Ph
 ,!
 8!
earth fault
&
&
1
max(I
Lx
, I
Ly
)<
2·min(I
Lx
, I
Ly
)
max(U
Lx
, U
Ly
)<
1.5·min(U
Lx
, U
Ly
)
Angle criteria
3I
0
>
 ,!
&
3I
0
I
Lx
earth fault
I
Ly
U
Lx–E
U
Ly–E
for load condition

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals