EasyManua.ls Logo

Siemens siprotec 7SA6 - Page 224

Siemens siprotec 7SA6
792 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
6-42 7SA6 Manual
C53000-G1176-C133-1
Figure 6-22 Short circuit of a phase-phase loop
The calculation of the phase-phase loop does not take place as long as one of the
concerned phases is switched off (during single-pole dead time), to avoid an incorrect
measurement with the undefined measured values existing during this state. A state
recognition (refer to Section 6.20) provides the corresponding block signal. A logic
block diagram of the phase-phase measuring system is shown in Figure 6-23.
Figure 6-23 Logic of the phase-phase measuring system
Phase–Earth Loops For the calculation of the phase-earth loop, for example during a L3–E short-circuit
(Figure 6-24) it must be noted that the impedance of the earth return path does not
correspond to the impedance of the phase. In the loop equation
Z
E
is replaced by (Z
E
/Z
L
)·Z
L
and the result is:
From this the line impedance can be extracted
I
L1
I
L2
Z
L
Z
L
L1
L2
L3
E
U
L2–E
U
L1–E
I
Lx
I
Ly
I
Lx
>
I
Ly
>
&
Measuring
System
L
x
–L
y
from state
recognition
R
x–y
; X
x–y
U
Lx
U
Ly
 ,SK!
I
L3
Z
L
I
E
Z
E
U
L3–E
=
I
L3
Z
L
I
E
Z
L
Z
E
Z
L
-------
U
L3–E
=
⋅⋅
Z
L
U
L3–E
I
L3
Z
E
Z
L
I
E
------------------------------------------
=

Table of Contents

Other manuals for Siemens siprotec 7SA6

Related product manuals