Appendix
B-55
7SA6 Manual
C53000-G1176-C133-1
10331 Uphph<< TimeOut (Uphph<< Time-
Out)
Voltage Protection OUT * * LED BO
10332 Uphph<(<) TRIP command
(Uphph<(<) TRIP)
Voltage Protection OUT * ON LED BO 73 132 2 GI
>Back Light on (>Light on) Device SP ON
OFF
* BI
>Cabinet door open (>Door open) Process Data SP on
off
* LED BI BO CB 101 1 1 GI
>CB waiting for Spring charged
(>CB wait)
Process Data SP on
off
* LED BI BO CB 101 2 1 GI
>Error Control Voltage (>ErrCntrlU) Process Data SP on
off
* LED BI BO CB 240 182 1 GI
>Error Meter (>Err Meter) Process Data SP on
off
* LED BI BO CB 240 184 1 GI
>Error Motor Voltage (>Err Mot U) Process Data SP on
off
* LED BI BO CB 240 181 1 GI
>SF6-Loss (>SF6-Loss) Process Data SP on
off
* LED BI BO CB 240 183 1 GI
>Transformer Danger (>Tx Danger) Process Data SP on
off
* LED BI BO CB 240 186 1 GI
>Transformer Temperature (>Tx
Temp.)
Process Data SP on
off
* LED BI BO CB 240 185 1 GI
Breaker (Breaker) Control Device CF_D12 on
off
* BO 240 160 1 GI
Breaker (Breaker) Control Device DP on
off
* BI CB 240 160 1 GI
Breaker OPENED (Brk OPENED) Device IntSP * * LED BO
CB1-TEST trip/close Phases L123
(CB1tst 123)
Testing - * *
CB1-TEST trip/close - Only L1
(CB1tst L1)
Testing - * *
CB1-TEST trip/close - Only L2
(CB1tst L2)
Testing - * *
CB1-TEST trip/close - Only L3
(CB1tst L3)
Testing - * *
Clock Synchronization (SynchClock) Device IntSP_Ev * * LED BO
Control Authority (Cntrl Auth) Control Authoriza-
tion
DP ON
OFF
* LED 101 85 1 GI
Control Authority (Cntrl Auth) Control Authoriza-
tion
IntSP ON
OFF
* LED
Controlmode LOCAL (ModeLOCAL) Control Authoriza-
tion
DP ON
OFF
* LED 101 86 1 GI
Controlmode LOCAL (ModeLOCAL) Control Authoriza-
tion
IntSP ON
OFF
* LED
Controlmode REMOTE (ModeRE-
MOTE)
Control Authoriza-
tion
IntSP ON
OFF
* LED
Disconnect Switch (Disc.Swit.) Control Device CF_D2 on
off
* BO 240 161 1 GI
F.No. Description Function Type of
Information
Log-Buffers Configurable in Matrix IEC 60870-5-103
Event Log On/Off
Trip (Fault) Log On/Off
Ground Fault Log On/Off
Marked in Oscill. Record
LED
Binary Input
Function Key
Binary Output
Chatter Blocking
Type
Information-No
Data Unit (ASDU)
General Interrogation

Table of Contents

Other manuals for Siemens siprotec 7SA6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens siprotec 7SA6 and is the answer not in the manual?

Siemens siprotec 7SA6 Specifications

General IconGeneral
BrandSiemens
Modelsiprotec 7SA6
CategoryRelays
LanguageEnglish

Related product manuals