Chapter 5 Display and Setting of Various Functions
5.4 Description of the Screen
HRL Series
5-48
By default
About continuous pump operation function
This function allows just the pump to continue operating after some alarms are activated.
Alarms that allow continuous pump operation are shown in Table 5.4-18 Alarms that allow
continuous pump operation (1/2) and Table 5.4-19 Alarms that allow continuous pump operation
(2/2).
“Continuous pump operation” ends if any one of the following conditions is met, and the product
stops operating:
(1) After activation of the alarm, the temperature has reached the “Pump operation sustainable
temperature” from the temperature at which pump-only operation starts.
(2) After activation of the alarm, the time reached the “Pump operation sustainable time” starting from
the time at which pump-only-operation started.
Table 5.4-18 Alarms that allow continuous pump operation (1/2)
Alarm
No.
Alarm name
Alarms that allow continuous
pump operation
Operation
CH1
CH2
AL01
CH1 Low Level FLT
[FLT]
×
AL02
CH1 Low Level WRN
[WRN]
-
-
AL03
CH2 Low Level FLT
[FLT]
×
AL04
CH2 Low Level WRN
[WRN]
-
-
AL06 2
Fan Inverter
[FLT]
AL07 3
Internal Cooling Fan
[WRN]
AL09
CH1 Hgih Temp. FLT
[FLT]
×
AL10
CH1 Hgih Temp.
[OFF]1/ [WRN]
-
-
[FLT]
AL11
CH1 Low Temp.
[OFF]1/ [WRN]
-
-
[FLT]
AL12
CH1 TEMP READY ALARM
[OFF]1 /[WRN]
-
-
[FLT]
AL13
CH2 High Temp. FLT
[FLT]
×
AL14
CH2 High Temp.
[OFF]1 / [WRN]
-
-
[FLT]
AL15
CH2 Low Temp.
[OFF]1 / [WRN]
-
-
[FLT]
AL16
CH2 TEMP READY ALARM
[OFF]1/ [WRN]
-
-
[FLT]
AL17
CH1 HX In High Temp. FLT
[FLT]
×
AL18
CH1 Press. Sensor
[OFF] / [WRN]
-
-
[FLT]1
×
AL19
CH1 High Press.
[OFF] / [WRN]
-
-
[FLT]1
×
AL20
CH1 Low Press.
[OFF] / [WRN]
-
-
[FLT]1
AL21
CH2 Press. Sensor
[OFF]/[WRN]
-
-
[FLT]1
×

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRL100-A 40 Series and is the answer not in the manual?

SMC Networks HRL100-A 40 Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRL100-A 40 Series
CategoryChiller
LanguageEnglish

Related product manuals