Chapter 7 Alarm Notifications and Troubleshooting
7.3 Troubleshooting
HRL Series
Table 7.3-2 Alarm codes and troubleshooting (2/2)
1 : Select from "OFF" / "WRN" / "FLT"
2 : Select from "OFF" / "WRN"
3 : The setting value can be changed.
4 : Setting the electrical conductivity only when option ‘D1’ is selected on CH1.
5 :Only for water-cooled type.
6 :Only for air-cooled type.
Sub code Operation Threshold
1 CH1 Pump maintenance 20,000h
2 Compressor maintenance 30,000h
3 Fan maintenance 6 30,000h
4 Dust-proof filter maintenance 6 500h 3
5 CH2 DI filter maintenance 500h 3
6 CH2 Pump maintenance 20,000h
8 Maintenance of CH1 circulating fluid
discharge pressure sensor
9 Maintenance of CH2 circulating fluid
discharge pressure sensor
10 Maintenance of CH2
circulating fluid flow sensor
11 CH1 DI filter maintenance4 500h 3
1 High compressor intake temp. 60ºC
2 Low compressor intake temp. 0ºC
5 Refrigeration circuit high press. rise
-
6 Refrigeration circuit high press. drop
-
8 Refrigeration circuit low press. drop
-
9 Refrigeration circuit low press. rise
-
11 Compressor running failure
-
12 Compressor discharge temp. rise
-
1 CH1 Circulating fluid temp. sensor
-
2 CH1 Heat exchanger inlet temp. sensor
-
3 Compressor discharge temp. sensor
-
4 Compressor intake temp. sensor
-
5 CH2 Heat exchanger outlet temp. sensor
-
9 Refrigeration circuit high press. sensor
-
10 Refrigeration circuit low press. sensor
-
13 CH2 Circulating fluid temp. sensor -
2 Internal communication error
-
Cause/Countermeasure
(Please reset the alarm after eliminating the cause.)
Refrigerant circuit failed.
・Check that the ambient temperature,
heat load satisfy the specifications.
・Check that the circulating fluid flow rate
is more than the minimum flow rate.
・Ask for the service.
"Maintenance reminder" occurred.
Please maintain the corresponding part.
Check that there is no abnormality with
the power supply system (e.g. ground fault,
short-circuit, voltage fluctuation, abnormal
interphase voltage, open phase, surge).
Compressor Inverter Comm.
Controller failed.
Shut off the power to this product and restart it.
If it does not return to normal, ask for service.
Short-circuit or broken wire of the sensor.
Ask for the service.