Chapter 7 Alarm Notifications and Troubleshooting
7.3 Troubleshooting
HRL Series
7-4
Table 7.3-2 Alarm codes and troubleshooting (2/2)
1 : Select from "OFF" / "WRN" / "FLT"
2 : Select from "OFF" / "WRN"
3 : The setting value can be changed.
4 : Setting the electrical conductivity only when option D1 is selected on CH1.
5 :Only for water-cooled type.
6 :Only for air-cooled type.
Sub code Operation Threshold
1 CH1 Pump maintenance 20,000h
2 Compressor maintenance 30,000h
3 Fan maintenance 6 30,000h
4 Dust-proof filter maintenance 6 500h 3
5 CH2 DI filter maintenance 500h 3
6 CH2 Pump maintenance 20,000h
7 Battery maintenance
8 Maintenance of CH1 circulating fluid
 discharge pressure sensor
9 Maintenance of CH2 circulating fluid
 discharge pressure sensor
10 Maintenance of CH2
circulating fluid flow sensor
11 CH1 DI filter maintenance4 500h 3
1 High compressor intake temp. 60ºC
2 Low compressor intake temp. 0ºC
3 Super heat temp. 0ºC
5 Refrigeration circuit high press. rise
6 Refrigeration circuit high press. drop
8 Refrigeration circuit low press. drop
9 Refrigeration circuit low press. rise
11 Compressor running failure
12 Compressor discharge temp. rise
1 CH1 Circulating fluid temp. sensor
2 CH1 Heat exchanger inlet temp. sensor
3 Compressor discharge temp. sensor
4 Compressor intake temp. sensor
5 CH2 Heat exchanger outlet temp. sensor
6 Ambient temp. sensor
9 Refrigeration circuit high press. sensor
10 Refrigeration circuit low press. sensor
12 CH2 DI sensor
13 CH2 Circulating fluid temp. sensor
15 CH1 DI sensor 4
1 EEPROM error
2 Internal communication error
3 FRAM error
5 Ref. memory error
6 Cir. memory error
AL40 FLT
AL41 FLT
AL42 FLT
AL43 FLT
AL44 FLT
AL45 FLT
Alarm
code
Alarm content
Default setting
Cause/Countermeasure
(Please reset the alarm after eliminating the cause.)
Maintenance
Abnormal
occurrence
AL37
Refrigeration Circuit
FLT
Refrigerant circuit failed.
Check that the ambient temperature,
heat load satisfy the specifications.
Check that the circulating fluid flow rate
is more than the minimum flow rate.
Ask for the service.
AL36
OFF 2
"Maintenance reminder" occurred.
Please maintain the corresponding part.
Compressor Inverter
Check that there is no abnormality with
the power supply system (e.g. ground fault,
short-circuit, voltage fluctuation, abnormal
interphase voltage, open phase, surge).
Compressor Inverter Comm.
CH1 Pump Inverter
CH1 Pump Inverter Comm.
CH2 Pump Inverter
CH2 Pump Inverter Comm.
Sensor
AL39
Controller
FLT
Controller failed.
Shut off the power to this product and restart it.
If it does not return to normal, ask for service.
AL38
FLT
Short-circuit or broken wire of the sensor.
Ask for the service.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRL100-A 40 Series and is the answer not in the manual?

SMC Networks HRL100-A 40 Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRL100-A 40 Series
CategoryChiller
LanguageEnglish

Related product manuals