C-50 Micro-Tech 9101/9201 Reference Manual, Rev J Thermo Fisher Scientific
The Micro-Tech has a built-in Ethernet port. Communications protocols
Ethernet/IP and Modbus/TCP can be used. The Micro-Tech is a Slave
device only, and cannot initiate messages. If the Micro-Tech loses power,
the Ethernet communication will take roughly 30 seconds to respond after
power is restored.
EtherNet/IP uses Ethernet physical layer network infrastructure.
EtherNet/IP can be easily confused as a simple combination of Ethernet
and the Internet Protocol. Instead, it is an industrial application layer
protocol used for communication between industrial control systems PLCs
and their components, such as a programmable logic controller or an I/O
system. The “IP” in EtherNet/IP, is not an abbreviation for “Internet
Protocol” but instead stands for “Industrial Protocol.”
Embedded Web Server
This is a future implementation and only simple data are available. The
Micro-Tech will respond with a static home page, when the address
“http://192.168.1.2” is entered in your browser window, as shown below.
Figure C–1. Thermo Fisher Static Home Page