6. To verify that the parameters are set correctly (the values are in the allowed range and
all parameters are valid), read the error counters with the command ERRORS.
If all values are valid, WMT700 sends the following response:
0,0,0,0
You can also use the G command to check that the parameters are set correctly.
If the response for parameter setting is not disabled (as instructed in step 3) but the
messages parameter is set to 1 instead, WMT700 responds to each S command
confirming the new parameter values. If an error occurs during the configuration,
WMT700 sends a response containing the error messages.
RS-485 is a half-duplex interface. If the RS-485 interface is used and response for
parameter setting is enabled (messages parameter is set to 1), a simple terminal
program cannot be used for loading parameters from
file.
This configuration file contains all the WMT700 parameters that are user-configurable.
For example:
S wndAvg,1.00000
S wndUnit,0
S wndDirOffset, 0.00000
S wndOrientation,0
S wndGustTime,3.00000
S wndCover,4
S wndVector,1
S wndCoast,0.00000
S autoInt,1.00000
S autoSend,0
S autoPort,1
S com1_baud,4
S com1_parity,0
S com1_data,8
S com1_stop,1
S com1_protocol,0
S com1_delay,20
S com2_baud,4
S com2_parity,0
S com2_data,8
S com2_stop,1
S com2_protocol,0
S com2_delay,20
S com2_interf,0
S sleepTime,5
S startDelay,5
S heaterOn,1.00000
S freqType,0
S aout1_o,0.00000
WMT700 User Guide M211095EN-H