TITANUS
MICRO·SENS
®
Maintenance
06/13
199
NOTICE
You must record the type of adjustment (air pressure-dependent or air
pressure-independent) and possibly the figures for air pressure, height
above sea level and voltage set, in the testing records.
4. Note the current air flow value during this maintenance session or check
it at the latest at the next inspection.
TIP
With the aid of the diagnosis software, all stored and current device data
and the settings input using the diagnosis tool can be stored as files.
5. If there is a similar ideal value deviation as before, interfering environ-
mental influences are the cause of this deviation. If these negative influ-
ences cannot be stopped from affecting air flow monitoring, the air flow
range must be increased.