TITANUS
MICRO·SENS
®
Maintenance
06/13
201
Testing Air Flow Monitoring
A break or a blockage in a pipe is displayed on the diagnostics tool “Mes-
sage” screen. Test air flow monitoring in accordance with the instructions
described in Chapter Commissioning "Air Flow Monitoring".
Testing Fault Forwarding
A fault is displayed on the TITANUS
MICRO·SENS
®
and possibly on the
FAS.
Proceed as described in Chapter Commissioning "Fault Forwarding".
Maintenance Intervals
The maintenance includes regular servicing. The air sampling smoke detec-
tion systems are checked during commissioning and annually thereafter.
For each service, the following checks must be carried out:
Type of Check Measure Other Information
in Chapter
Servicing Visual check
Detection unit and
alarm forwarding
Check pipe system
Air flow sensor adjustment
Air flow monitoring
Fault forwarding
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
Commissioning
In addition to the annual maintenance national regulations and standards re-
ferring to the intended use must be considered, as well as application-
specific requirements, if necessary.
9.11
9.12
9.13