WAGNER Titanus Micro-Sens - Projection Tables for System Design

WAGNER Titanus Micro-Sens
238 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Classification TITANUS MICRO·SENS
®
Projection without filter
Type
Sensitivity
(% Lt/m)
Number of points
1 2 3 4 5 6 7 8
DM-TM-10
0,1
A A A A A A A A
0,2 A A A A A A B B
0,3 A A A A B B B B
0,4 A A A B B B B C
DM-TM-50
0,5
A A B B B B
C
C
0,6 A A
B B
B
C C C
0,7 A
B B B C C C C
0,8 A
B B C C C C C
0,9 A
B B C C C C C
1 A
B B C C C C C
1,1 A
B
C C C C C C
1,2 A
B C C C C C C
1,3
B
B C C C C C
1,4
B B C C C C
1,5
B B C C C C
1,6
B
C C C C C
1,7
B C C C C
1,8
B C C C C
1,9
B C C C C
2
B C C C
Without pipe accessories or with detector box or VSK
Pipe shape U
Fan
󰇟V󰇠 1 2 3 4 5 6 7 8
I
9
40 40 40 40 40
permitted total pipe
length [m]
U
9
50 50 50 50 50 50 50 50
M
9
50 50 50 50 50 50 50 50
Double U
9
50 50 50 50 50 50 50 50
With OXY·SENS and detector box or with steam trap or with VSK and detector box
Pipe shape U
Fan
󰇟V󰇠 1 2 3 4 5 6 7 8
I
9
40 40 40
permitted total pipe
length [m]
U
9
50 50 50 50 50 50
M
9
50 50 50 50 50 50
Double U
9
50 50 50 50 50 50 50 50