Technical Description
TITANUS
MICRO·SENS
®
50
06/13
In order to extend the maintenance intervals, one air filter can be installed in
every output pipe instead of one air filter inside the main sampling pipe. The
same design specifications shall apply as stated in the projection tables in
the appendix.
LF-ADLF-ADLF-ADLF-AD
TITANUS
®
Figure 31: LF-AD filter in the main sampling pipe
Furthermore, in order to extend the maintenance intervals, several air filters
can be installed in parallel in the main sampling pipe. This requires the main
sampling pipe to be split into one or several pipes and to be equipped with
the same air filter or the combination of air filters. The individual pipes can
then alternatively be either combined again to one main sampling pipe or be
separately continued into the monitoring area(s). The same design specifica-
tions for the individual air filters shall apply as stated in the projection tables
in the appendix.