4.2 Motion Command Details
4.2.11 SCC (Change Filter Time Constant)
4
Motion Control Program Commands and Instructions
4-67
Monitor Parameters
Timing Charts
Normal Completion
Error Completion
Register
Address
Name Monitored Contents
IL
02 Warnings This parameter reports the current warning status.
IL04 Alarms This parameter reports the current alarm status.
IW
08
Motion Command
Response Code
This parameter shows the motion command currently in execution.
This parameter is 12 during execution of the SCC command.
IW09
Bit 0
Command Execu-
tion Flag
This bit is 1 (Processing) during execution of the SCC command. The bit
changes to 0 (Completed) when execution ends.
IW
09
Bit 1
Command Hold
Completed
This bit is always 0 (Command hold not completed) for the SCC com-
mand.
IW
09
Bit 3
Command Error End
This bit changes to 1 (Completed with an error) when an error occurs
during execution of the SCC command.
The axis will decelerate to a stop if it is moving. This bit changes to 0
(Completed normally) when another command is executed.
IW09
Bit 8
Command Execu-
tion Completed
This bit changes to 1 (Normal execution completed) when execution of
the SCC command ends.
OW08 = 12 (SCC)
IW08 = 12 (SCC)
IW09 Bit 0 (BUSY)
IW09 Bit 8 (COMPLETE)
IW09 Bit 3 (FAIL)
This interval is not
constant.
OW08 = 12 (SCC)
IW08 = 12 (SCC)
IW09 Bit 0 (BUSY)
IW09 Bit 8 (COMPLETE)
IW09 Bit 3 (FAIL)
This interval is not
constant.