10.5  Motion Parameter Details
10.5.1  Fixed Parameter List
10-35
10.5
Motion Parameter Details
This section describes the fixed parameters, setting parameters, and monitor parameters that 
can be set in the SVC Definition Tab Page for the connected Inverters.
10.5.1
Fixed Parameter List
No. Name and Contents Setting Range Default Setting
0
Selection of Operation Mode 0 or 1 0
Sets the run mode to send/receive commands to/from the Inverter through MECHATROLINK.
0: Normal Operation Mode (default)
Inverter operation is performed.
1: Axis Unused
Impossible to send/receive commands.
1 Reserved −−
2
Function Selection Flag 2 − 0
Bit 0:
Communication 
Abnormality Detec-
tion Mask
Specifies whether to mask an error to be reported to the monitor parameter when 
an error is detected in MECHATROLINK communications.
0: Disabled (default)
When a communication error occurs, the error will be reported in the Alarm or 
Warning monitor parameter.
1: Enabled
When a communication error occurs, the error will not be reported in the Alarm or 
Warning monitor parameter.
Bit 1:
WDT Abnormality 
Detection Mask 
(Applicable only for 
synchronous com-
munications sup-
ported inverters)
Specifies whether to mask an error to be reported to the monitor parameter when 
a synchronization management error is detected in MECHATROLINK communica-
tions.
0: Disabled (default)
If a watchdog error occurs in communications with the Inverter, the error will be 
reported in the Alarm monitor parameter.
1: Enabled
If a watchdog error occurs in communications with the Inverter, the error will not 
be reported in the Alarm monitor parameter.
Bits 2 to F Reserved
3
Function Selection Flag 3 − 8000H
Bit 0:
Communication 
Selection Is Abnor-
mal
Valid when Communication Abnormality Detection Mask bit (bit 0) of Communica-
tions Selection Flag 2 is set to 0 (Disabled).
Specifies whether an Alarm or Warning is to be output when a communication 
errors occurs.
0: Alarm (default)
Outputs Alarm at occurrence of communication error.
The alarm must be reset to restart communications.
1: Warning
Outputs Warning at occurrence of communication error.
When communications is restored, the warning will be automatically cleared.
Bits 1 to E Reserved
Bit F:
Parameter Discrim-
ination Flag
Reserved
1: Inverter parameter (always ON)
4 to 
63
Reserved −−