4.2 Motion Command Details
4.2.11 SCC (Change Filter Time Constant)
4-66
4.2.11
SCC (Change Filter Time Constant)
The SCC command transfers the set value of the OW3A setting parameter (Filter Time
Constant) to the Moving Average Time or Exponential Acceleration/Deceleration Time Constant
SERVOPACK parameter and enables the setting.
Execution and Operating Procedures
1.
Make sure that all of the following conditions are met.
* Before you change to this command during the execution of another command, you must check whether
the command can be changed and how operation changes when the command is changed. Refer to the
following section for details on changing from another command.
4.4 Changing the Command on page 4-137
2.
Set the OW08 setting parameter (Motion Commands) to 12 to execute the SCC
motion command.
The SERVOPACK parameter to which the value of OW3A is transferred will depend on the filter
type that has been set.
No filter or moving average filter: Moving Average Time
Exponential acceleration/deceleration filter: Exponential Acceleration/Deceleration Time Constant
The IW08 monitor parameter (Motion Command Response Code) is 12 during execution of this
command.
During command processing, bit 0 (Command Execution Flag) in the IW09 monitor parameter
will change to 1 (Processing). When processing is completed, this bit will change to 0 (Completed).
3.
Set OW08 to 0 to execute the NOP motion command.
This concludes the process for changing the filter time constant.
Holding and Canceling Commands
Bit 0 (Hold Command) and bit 1 (Cancel Command) in the OW09 setting parameter can-
not be used to stop the axis.
Related Parameters
The parameters that are related to this command are listed in the following table.
Setting Parameters
An SVC Function Module can automatically transfer setting parameters to SERVOPACK parame-
ters when they are overwritten. The SCC command is not required if this function is used. Refer
to the following section for details.
3.4 Motion Parameter Details −
Function Selection Flags 1−
Bit A: SERVOPACK Parameter Auto-
Write on page 3-29
No. Execution Condition Confirmation Method
1 There must be no alarms. Both IL02 and IL04 must be 0.
2 Distribution has been completed. Bit 0 in IW0C must be 1.
3
Motion command execution for the target axis
must be completed.*
IW08 must be 0 and bit 0 in
IW09 must be 0.
Register
Address
Name Setting Details
OW
03 Function Settings 1 Select the speed unit, acceleration/deceleration unit, and filter type.
OW08 Motion Commands Set this parameter to 12 (SCC) to change the filter time constant.
OW09
Bit 0
Hold Command This bit is ignored for the SCC command.
OW
09
Bit 1
Cancel Command This bit is ignored for the SCC command.
OW
3A Filter Time Constant Set the acceleration/deceleration filter time constant.