EasyManua.ls Logo

YASKAWA SVC - Alarm and Warning Codes for Inverter; 10.6.1 A1000

YASKAWA SVC
623 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.6 Alarm and Warning Codes for Inverter
10.6.1 A1000
10-64
10.6
Alarm and Warning Codes for Inverter
There are the following four types of inverter alarms and warnings for different detection loca-
tions and error contents.
* SI-ET3: MECHATROLINK Option Card for Inverter
Note: 1. If more than one error is detected at the same time, the SI-ET3 gives priority to the error with the lowest
alarm code.
2. When an error is detected while another is being detected, the alarm code will not be refreshed.
3. If more than one minor failure (warning) is detected at the same time, the SI-ET3 gives priority to the error
with the lowest warning code number.
Inverter alarms and warnings are described below.
10.6.1
A1000
Inverter Alarms
Error Type Description
Place the Error
Occurred
Alarm
Inverter Alarm
Serious failure that can damage the inverter
and machine
Inverter
MECHATROLINK-III Command
Error and MECHATROLINK-III
Communications Error
MECHATROLINK communications failure SI-ET3*
Warning
Inverter Warning
Incorrect operation or minor failure that will
not likely result in a serious situation.
Inverter
MECHATROLINK-III Command
Error and MECHATROLINK-III
Communications Error
MECHATROLINK communications error
warning
SI-ET3*
Alarm Code
(IW19
*1
/IW32
*2
)
Digital Operator
Display
Name
CPF00 or CPF01 Control Circuit Error
oFA03 Option Card Error Occurred at Option Port CN5-A
oFA04 Option Card Error Occurred at Option Port CN5-A
oFb03 Option Card Error Occurred at Option Port CN5-B
oFb04 Option Card Error Occurred at Option Port CN5-B
oFb07 to oFb09 Option Card Error Occurred at Option Port CN5-B
oFC03 Option Card Error Occurred at Option Port CN5-C
oFC04 Option Card Error Occurred at Option Port CN5-C
oFC07 to oFC09 Option Card Error Occurred at Option Port CN5-C
0002H Uv1 DC Bus Undervoltage
0003H Uv2 Control Power Supply Voltage Fault
0004H Uv3 Undervoltage 3 (Soft-charge Bypass Circuit Fault)
0005H SC Output Short-Circuit or IGBT Fault
0006H GF Ground Fault
0007H oC Overcurrent
0008H ov Overvoltage
0009H oH Heatsink Overheat
000AH oH1 Overheat 1 (Heat sink Overheat)
000BH oL1 Motor Overload
000CH oL2 Drive Overload
000DH oL3 Overtorque Detection 1
000EH oL4 Overtorque Detection 2
000FH rr Dynamic Braking Transistor
Continued on next page.

Table of Contents

Related product manuals