7.2 MECHATROLINK Communications Settings
7.2.2 MECHATROLINK Detail Definition Dialog Box Details
7-8
7.2.2
MECHATROLINK Detail Definition Dialog Box Details
The MECHATROLINK Detail Definition Dialog Box has four tab pages: Transmission Parame-
ters, Link Assignment, I/O Map, and Status. Click the tab to view each tab page.
Transmission Parameters Tab Page
The items on the Transmission Parameters Tab Page are described in the following table.
Refer to the following section for details on each item.
Item Details on page 7-8
Item Details
This section provides details on the items that are displayed on the Transmission Parameters
Tab Pag e.
No. Item Description Default
Master/Slave
Set whether to use the SVC Function Module as a
master or a slave station.
Master
My station address Sets the local station address. 01 hex
Communication Cycle Sets the transmission cycle.
250
μ
s
Enabled message com-
munication
Enables or disables message communications. Enable
Number of retry to slaves
Sets the maximum number of retries to execute within
one transmission cycle.
1
Number of connection Sets the number of connected slave stations. 8
Slave synchronous func-
tion
Enables or disables slave CPU synchronization. Disabled
Message Box
Displays precautions on the high-speed scan time set-
ting.
Always save all settings to the flash memory after you change them.
Important