5.2 Absolute Encoders
5.2.6 Position Management Method for Each Machine Operation Type
5-30
2.
Check the current value of OL
48 in the Setting Parameter Area, and then calculate
value with the following formula and set that value in OL
48. (OL
48: Zero Point
Position Offset in Machine Coordinate System) - (IL
10: Machine Coordinate Sys-
tem Calculated Position (CPOS))
3.
Check that the current value and setting data value are the same for OL
48.
4.
Click the Write Button.
The set value is saved to the MP3000.
5.
Select Online
−
Save to Flash from the menu bar of the MPE 720 Ver.7 window.
The setting is saved to flash memory.
6.
Set the origin with the ZSET command.
After performing the above procedure, the saved value is stored automatically in OL
48
when the power supply is turned OFF and ON again.