10.3 Precautions for Inverter Operation
10-18
Command Error Completed Status
If Drive Permission is turned OFF during execution of the Inverter Drive Control command,
Command Error Completed Status (IW09 bit 3) turns ON. To clear the Command Error
Completed Status, change the command to NOP and perform the recovery operation.
The recovery procedure is the same as steps 5 to 9 of the procedure in
Turning OFF Drive
Permission on page 10-17, on the previous page.
Note: You cannot use Alarm Clear in the Command Error Completed Status.
Inverter Drive Control (= 1)
You cannot use
Alarm Clear in the
Command Error
Completed Status.
The Inverter Drive Control command
is being maintained, so Drive
Permission cannot be turned ON.
Main circuit
power supply
Command
(OW08)
Forward RUN or
Reverse RUN
(OW10 bit 0 or 1)
Device Warning
Occurrence
(IW2C bit 1)
Device Alarm
Occurrence
(IW2C bit 0)
Inverter Ready
(IL2A bit 6)
Operation Ready
(IW00 bit 0)
Command Error
Completed Status
(IW09 bit 3)
Alarm Clear
(OW00 bit F)
Drive Permission
(OW00 bit D)