10.4  Main Commands and Subcommands
10.4.3  Main Command Details
10-22
 Setting Parameters
 Monitor Parameters
Name Register No.
Setting 
Range
Remarks
Mode Settings 1 OW01 Bit −
Command OW08 0 to 8 01: Inverter Drive Control
Output Data Option Selec-
tion
OW0C Bit −
Input Data Option Selection OW0D Bit −
Input Command OW10 Bit −
Speed Reference OW11 −−
Torque Reference OW12 −−
Torque Compensation  
(Option)
OW13 −
Enabled when the Output Data Option Selection 
(OW0C), bit 0 is ON.
Analog Output Terminal 1 
Output
OW14 −
Enabled when the Output Data Option Selection 
(OW0C), bit 1 is ON.
Analog Output Terminal 2 
Output
OW15 −
Enabled when the Output Data Option Selection 
(OW0C), bit 2 is ON.
Terminal Output OW16 −
Enabled when the Output Data Option Selection 
(OW0C), bit 3 is ON.
PID Target OW17 −
Enabled when the Output Data Option Selection 
(OW0C), bit 4 is ON.
Pulse Train Output OW18 −
Enabled when the Output Data Option Selection 
(OW0C), bit 5 is ON.
V/f Gain OW19 −
Enabled when the Output Data Option Selection 
(OW0C), bit 6 is ON.
Command Selection OW1B −
Enabled when the Output Data Option Selection 
(OW0C), bit 8 is ON.
Name Register No.
Setting 
Range
Remarks
Warning IL02 Bit −
Alarm IL04 Bit −
Command Response Code IW08 0 to 8 01: Inverter Drive Control
Command Status IW09 Bit
Bit 0 (Command execution 
flag)
ON while the com-
mand is being exe-
cuted
Bit 3 (Command error com-
pleted status)
ON when an error 
occurs during 
command pro-
cessing
Bit 8 (Command execution 
completed)
OFF during com-
mand execution, 
and ON when 
command execu-
tion is completed.
Input Data Option Selection 
Monitor
IW0D Bit −
Output Frequency IW11 −−
Output Current IW12 −−
Motor Speed (Option) IW13 −
Enabled when Input Data Option Selection 
(OW0D), bit 0 is ON.
Torque Reference (Option) IW14 −
Enabled when Input Data Option Selection 
(OW0D), bit 1 is ON.
Encoder Count PG1 IW15 −
Enabled when Input Data Option Selection 
(OW0D), bit 2 is ON.
Continued on next page.