10.4 Main Commands and Subcommands
10.4.4 Subcommand Details
10-30
Monitor Parameters
Name Register No.
Setting
Range
Remarks
Subcommand Response Code IW0A
0 to
65535
01: Inverter I/O Control
Subcommand Status IW0B Bit
Bit 0 (Command execution
flag)
ON during execu-
tion.
Bit 3 (Command error com-
pleted status)
ON when an error
occurs during the
command pro-
cessing
Bit 8 (Command execution
completed)
OFF during exe-
cution, and
always ON after
execution is com-
pleted.
Auxiliary Input Data Option
Selection Monitor
IW0F Bit −
Motor Speed (Option) IW13 −
Enabled when bit 0 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Torque Reference (Option) IW14 −
Enabled when bit 1 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Encoder Count PG1 IW15 −
Enabled when bit 2 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Frequency Reference (Option) IW16 −
Enabled when bit 3 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Analog Input A2 IW17 −
Enabled when bit 4 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Main Bus Voltage (Option) IW18 −
Enabled when bit 5 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Alarm Code IW19 −
Enabled when bit 6 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Warning Code IW1A −
Enabled when bit 7 of Auxiliary Input Data Option
Selection (OW0F
) is ON.
Multi-Fun
ction Output Terminal IW1B −
Enabled when bit 8 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Analog Input A3 IW1C −
Enabled when bit 9 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Multi-Function Input Terminal IW1D −
Enabled when bit A of Auxiliary Input Data Option
Selection (OW0F) is ON.
Analog Input A1 IW1E −
Enabled when bit B of Auxiliary Input Data Option
Selection (OW0F) is ON.
Encoder Count PG2 IW1F −
Enabled when bit C of Auxiliary Input Data Option
Selection (OW0F) is ON.
Monitor data set in F6-23 IW20 −
Enabled when bit D of Auxiliary Input Data Option
Selection (OW0F) is ON.
Monitor data set in F6-24 IW21 −
Enabled when bit E of Auxiliary Input Data Option
Selection (OW0F) is ON.
M-III Sub Command Status IW31 Bit Inverter subcommand processing status
Auxiliary Inverter Alarm Code IW33
0 to
FFFFH
Inverter alarm code