EasyManua.ls Logo

YASKAWA SVC - Page 532

YASKAWA SVC
623 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.4 Main Commands and Subcommands
10.4.4 Subcommand Details
10-30
Monitor Parameters
Name Register No.
Setting
Range
Remarks
Subcommand Response Code IW0A
0 to
65535
01: Inverter I/O Control
Subcommand Status IW0B Bit
Bit 0 (Command execution
flag)
ON during execu-
tion.
Bit 3 (Command error com-
pleted status)
ON when an error
occurs during the
command pro-
cessing
Bit 8 (Command execution
completed)
OFF during exe-
cution, and
always ON after
execution is com-
pleted.
Auxiliary Input Data Option
Selection Monitor
IW0F Bit
Motor Speed (Option) IW13
Enabled when bit 0 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Torque Reference (Option) IW14
Enabled when bit 1 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Encoder Count PG1 IW15
Enabled when bit 2 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Frequency Reference (Option) IW16
Enabled when bit 3 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Analog Input A2 IW17
Enabled when bit 4 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Main Bus Voltage (Option) IW18
Enabled when bit 5 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Alarm Code IW19
Enabled when bit 6 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Warning Code IW1A
Enabled when bit 7 of Auxiliary Input Data Option
Selection (OW0F
) is ON.
Multi-Fun
ction Output Terminal IW1B
Enabled when bit 8 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Analog Input A3 IW1C
Enabled when bit 9 of Auxiliary Input Data Option
Selection (OW0F) is ON.
Multi-Function Input Terminal IW1D
Enabled when bit A of Auxiliary Input Data Option
Selection (OW0F) is ON.
Analog Input A1 IW1E
Enabled when bit B of Auxiliary Input Data Option
Selection (OW0F) is ON.
Encoder Count PG2 IW1F
Enabled when bit C of Auxiliary Input Data Option
Selection (OW0F) is ON.
Monitor data set in F6-23 IW20
Enabled when bit D of Auxiliary Input Data Option
Selection (OW0F) is ON.
Monitor data set in F6-24 IW21
Enabled when bit E of Auxiliary Input Data Option
Selection (OW0F) is ON.
M-III Sub Command Status IW31 Bit Inverter subcommand processing status
Auxiliary Inverter Alarm Code IW33
0 to
FFFFH
Inverter alarm code

Table of Contents