Parameters 217
RECOMMENDED
Drive stores the light load direction at each start to
non volatile memory.
2
10.83 FLOOR LIM
SWITCH
Selects the source from which the Lift control
program reads the floor limit switch signal. This
signal is activated when the lift reaches any of the
floors and when any of the floor limit switches is hit. 1
= Lift has reached the floor position. 0 = Lift is not in
the floor position.
C.FALSE/
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
10.84 INSPECTION
MODE
Selects the source for enabling/disabling the
inspection mode.
1 = Inspection mode is enabled.
0 = Inspection mode is disabled.
Enabling the inspection mode also enables
parameters 10.85 INSPECTION UP and 10.86
INSPECTION DOWN. For more information, see
section Inspection mode on page 135.
C.FALSE/
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
10.85 INSPECTION UP
Selects the source for starting the lift in the upward
direction when the inspection mode is enabled with
parameter 10.84 INSPECTION MODE.
1 = Lift is started in the upward direction.
0 = Lift is not moving in the upward direction.
C.FALSE/
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
10.86 INSPECTION
DOWN
Selects the source for starting the lift in the
downward direction when the inspection mode is
enabled with parameter 10.84 INSPECTION MODE.
1 = Lift is started in the downward direction.
0 = Lift is not moving in the downward direction.
C.FALSE/
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
No. Bit/Name/Value/
Range
Description Def/Type
FbEq
(16b/32b)