248 Parameters
46.10 MOT TEMP FLT LIM
Defines the fault limit for motor overtemperature
protection (when parameter 46.07 MOT TEMP
PROT = Fault).
110 °C/
INT32
0…10000 °C Motor overtemperature fault limit. 1 = 1 °C / -
46.80 FAULT RESET
Selects the source for the external fault reset signal.
The signal resets the drive after a fault trip if the
cause of the fault no longer exists. 1 = Fault reset.
DIO1 / Bit
pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
46.81 AUTORESET
TRIALS
Defines the number of automatic fault resets the
drive performs within the trial time defined with
parameter 46.82 AUTORST TRL TIME.
The faults to be reset are defined with parameter
46.84 AUTORESET SEL. For more information on
the Automatic fault reset function, see section
Automatic fault reset on page 133.
3/ UINT32
0…5 The number of the automatic fault resets allowed.
- / 1 = 1
46.82 AUTORST TRL
TIME
Defines the time within which automatic fault resets
are performed after the drive has tripped on a fault.
30.0 s/ Real
1.0…600.0 s Trial time for automatic fault resets.
- / 10 = 1 s
46.83 AUTORESET
DELAY
Defines for how long the drive will wait after a fault
before attempting an automatic fault reset.
1.0 s/ Real
0.0…120.0 s Resetting delay.
- / 10 = 1 s
No. Bit/Name/Value/
Range
Description Def/Type
FbEq
(16b/32b)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACL30 and is the answer not in the manual?

ABB ACL30 Specifications

General IconGeneral
BrandABB
ModelACL30
CategoryDC Drives
LanguageEnglish

Related product manuals