Parameters 253
50.08 FBA SW B12 SRC
Selects the source for freely programmable fieldbus
status word bit 28 (02.11 FBA MAIN SW bit 28). Note
that this functionality may not be supported by the
fieldbus communication profile.
C.False /
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
50.09 FBA SW B13 SRC
Selects the source for freely programmable fieldbus
status word bit 29 (02.11 FBA MAIN SW bit 29). Note
that this functionality may not be supported by the
fieldbus communication profile.
C.False /
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
50.10 FBA SW B14 SRC
Selects the source for freely programmable fieldbus
status word bit 30 (02.11 FBA MAIN SW bit 30). Note
that this functionality may not be supported by the
fieldbus communication profile.
C.False /
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
50.11 FBA SW B15 SRC
Selects the source for freely programmable fieldbus
status word bit 31 (02.11 FBA MAIN SW bit 31). Note
that this functionality may not be supported by the
fieldbus communication profile.
C.False /
Bit pointer
Bit pointer: CONST or POINTER (See Terms and
abbreviations on page 183.)
50.12 FBA CYCLE TIME Selects the communication speed (cycle time) for the
fieldbus interface.
Fast / enum
Slow
The communication cycle time is 10 ms. 0
Normal
The communication cycle time is 2 ms. 1
Fast
The communication cycle time is 2 ms. 2
50.13 FBA MAIN SW
FUNC
Status Word for fieldbus communication. 0b011 / Pb
0b000...0b111 Fieldbus main status function. 1 = 1
No. Bit/Name/Value/
Range
Description Def/Type
FbEq
(16b/32b)
Bit Name Value Information
(continued)
0 Run enable func
1...2 Not used