Parameters 193
02.11 FBA MAIN SW
Status Word for fieldbus communication. - / Pb
0x00000000...
0xFFFFFFFF
Fieldbus main status word. 1 = 1
02.12 FBA MAIN REF1
Scaled fieldbus reference 1. See parameter
50.04 FBA REF1 MODESEL.
0/ INT32
-2147483647...
2147483647
Scaled fieldbus reference 1. - / 1 = 1
02.13 FBA MAIN REF2
Scaled fieldbus reference 2. See parameter
50.05 FBA REF2 MODESEL.
0/ INT32
-2147483647...
2147483647
Scaled fieldbus reference 2. - / 1 = 1
02.14 FEN DI STATUS
Status of digital inputs of FEN-xx encoder interfaces
in drive option Slots 1 and 2. Examples:
000001 (01h) = DI1 of FEN-xx in Slot 1 is ON, all
others are OFF.
000010 (02h) = DI2 of FEN-xx in Slot 1 is ON, all
others are OFF.
010000 (10h) = DI1 of FEN-xx in Slot 2 is ON, all
others are OFF.
100000 (20h) = DI2 of FEN-xx in Slot 2 is ON, all
others are OFF.
- / Pb
0b000000...
0b111111
FEN-xx digital input status. 1 = 1/ -
No. Bit/Name/Value/
Range
Description Def/Type
FbEq
(16b/32b)
Bit Name Value Information
(continued)
14 REV ACT 1 Drive is running in reverse direction.
0 Drive is running in forward direction.
15 RESERVED
16 FAULT 1 Fault is active. See chapter Fault tracing.
0 No fault is active.
17 LOCAL
PANEL
1 Local control is active, ie, drive is controlled from PC tool or
control panel.
0 Local control is inactive.
18...
26
RESERVED
27 REQUEST
CTL
1 Control word is requested from fieldbus.
0 Control word is not requested from fieldbus.
28...
31
SW B28...
SW B31
Programmable status bits (unless fixed by the used profile). See
parameters 50.0850.11 and the user’s manual of the fieldbus
adapter.