5-82
Chapter 5. Functions
z Sample settings
Event
Event Display Internal event 1 Internal event 2
Operation type
E
_
.C1
9:
Deviation high and low
limits (final SP reference)
32: Timer (status)
Direct/Reverse
E
_
.C2
1: Reverse ----
Standby
E
_
.C2
0: No standby ----
Event state in
READY
E
_
.C2
1: Forced OFF 0: Continues
Alarm OR
E
_
.C3
0: None 0: None
Special OFF
E
_
.C3
0: No special OFF ----
Delay time unit
E
_
.C3
0: 0.1 s 0: 0.1 s
Event main
setting (low limit)
E
_
3 ----
Event sub-setting
(high limit)
E
_
.SB
3 ----
Hysteresis
E
_
.HY
9999 ----
ON delay
E
_
.ON
2 15
OFF delay
E
_
.OF
0 0
_ : Internal event No.
DI assignment
DI assignment Display Internal contact 1 Internal contact 2
Operation type
DI
_
.1
7: RUN/READY 17: Timer stop/start
Input bit function
DI
_
.2
1: Function 1, (A and B) or (C
and D)
1: Function 1, (A and B) or (C
and D)
Input assignment
A
DI
_
.3
18: User-defined bit 1 10: Internal event 1 (setting
= 9: Deviation high
and low limits (final SP
reference))
Input assignment
B
DI
_
.4
11: Internal event 2 (setting
= 32: Timer (status))
26: During SP ramp
Input assignment
C
DI
_
.5
0: Normally open (normally
OFF = 0)
18: User-defined bit 1
Input assignment
D
DI
_
.6
0: Normally open (normally
OFF = 0)
11: Internal event 2 (setting
= 32: Timer (status))
Polarity A
DI
_
.7
0: Direct 0: Direct
Polarity B
DI
_
.7
1: Reverse 1: Reverse
Polarity C
DI
_
.7
0: Direct 0: Direct
Polarity D
DI
_
.7
0: Direct 0: Direct
Polarity
DI
_
.8
1: Reverse 0: Direct
Internal event No.
assignment
DI
_
.9
---- 2