6-21
Chapter 6. Displayed Items and Settings
Display Item Description Initial
value
User
level
Notes
C 33
STEP time unit 0: 0.1 s
1: 1 s (displayed as min.s on the console)
2: 1 min (displayed as h.min on the
console)
C 34
STEP PV start 0: No
1: Up start
2: Down start
C 35
STEP loop 0: Operation stops (no loop-back)
1: Loops back
2: Continues SOAK with the final step’s SP
(no loop-back)
C 36
CT1 operation type 0: Heater burnout detection
1: Current measurement
0 0 Displayed if a model with two CT
inputs is used.
C 37
CT1 output 0: Control output 1
1: Control output 2
2: Event output 1
3: Event output 2
4: Event output 3
0 0 Displayed if a model with two CT
inputs is used and CT1 operation
type is set to heater burnout
detection (C36 = 0).
C 38
CT1 measurement
wait time
30 to 300 ms 30 0
C 39
CT2 operation type 0: Heater burnout detection
1: Current measurement
0 0 Displayed if a model with two CT
inputs is used.
C 40
CT2 output 0: Control output 1
1: Control output 2
2: Event output 1
3: Event output 2
4: Event output 3
0 0 Displayed if a model with two CT
inputs is used and CT2 operation
type is set to heater burnout
detection (C39 = 0).
C 41
CT2 measurement
wait time
30 to 300 ms 30 0
C 42
Control output 1
range
1: 4–20 mA
2: 0–20 mA
1 0 Displayed if current output is
set as control output 1 by the
model No.
The decimal point position of
scaling low and high limits
If “Control output 1 type” is set to
MV or CT: 1 digit after the
decimal point
PV or SP: the same as the PV
decimal point position
The unit for scaling low and high
limits
If “Control output 1 type” is set to
MV: %
PV or SP: the same as the PV unit
CT: A (current)
C 43
Control output 1
type
0: MV
1: Heating MV (for heating/cooling
control)
2: Cooling MV (for heating/cooling
control)
3: PV
4: PV (before applying ratio, bias, filter)
5: SP
6: Deviation
7: CT1 current
8: CT2 current
9: Invalid
10: SP+MV
11: PV+MV
0 0
C 44
Control output 1
scaling low limit
−1999 to +9999
The decimal point position and unit vary
depending on the setting for control
output 1 type” (C43).
0.0 0
C 45
Control output 1
scaling high limit
100.0 0