9-12
Chapter 9. PLC Link Communication Function
Transfer setting examples
z
Cyclic data transfer (PLC C1M)
Used for writing parameters from the PLC to the C1M consecutively.
In this example, data at D0000100 to D0000103 are transferred to the C1M
periodically.
z Transfer operation settings
Transfer type: Cyclic transfer (PLCC1M)
Live notification device: M000100
Completion notification bit: M0000010
Completion notification data: D000010
Note
0 and 1 are written alternately to the live notification device periodically.
If [Notification device initialization] on the [Common] tab is set to 0
(enabled), 0 is written to the device specified by [Completion notification
bit] immediately before the data transfer.
After the data transfer, “1” is written to the completion notification bit.
If the data transfer is successful, 0 is written to the device specified by
[Completion notification data]. If there is an error in the transfer, a value
other than 0 is written to the device.