EasyManua.ls Logo

Azbil C1M - Page 255

Azbil C1M
306 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9-17
Chapter 9. PLC Link Communication Function
9 - 4 List of PLC Link Settings
The PLC link settings include common settings, transfer settings, and data settings.
Common settings
Item Settings Initial
value
Notes
PLC Link Function 0: Disabled
1: Enabled
0
PLC Link Operation at Power On 0: PLC link operation stops when the
power is turned on.
1: PLC link operation is executed when
the power is turned on.
0 The setting is valid only if [PLC Link
Function] is set to 1.
PLC Link Operation 0: Stop
1: Execute
0 The setting is valid only if [PLC Link
Function] is set to 1.
Max. No. of units connected by
PLC link
8, 16, 24, 31 8
Startup delay time 0–60 s 5
Trigger device initialization 0: No
1: Yes
0
Notification device initialization 0: No
1: Yes
0
Station address 0–127 0 The address of the PLC to
communicate with
TimeOut 0–32000 ms 1000
Send Delay Time 0–1000 ms 5
Handling Precautions
When connecting to a Mitsubishi PLC, set the timeout time to 4000 ms or
longer. If a time shorter than 4000 ms is set, faulty communication may result,
depending on the configuration of the Mitsubishi PLC, etc.

Table of Contents

Related product manuals