9-18
Chapter 9. PLC Link Communication Function
Transfer settings
Transfer sheets 1 to 4 can be set independently.
Item Settings Initial value Notes
Transfer: Enabled/Disabled Unchecked: Disabled
Checked: Enabled
Unchecked
Transfer type
Cyclic data transfer (PLC → C1M)
Cyclic data transfer (C1M → PLC)
Triggered data transfer (PLC → C1M)
Triggered data transfer (C1M → PLC)
None
Trigger device address When trigger device is PLC
See the list of address ranges for the
PLC device type.
Usable devices (p.9-6)
When trigger device is the C1M
Selectable from the C1M monitor data
and parameters.
Not set For triggered data transfer
Live notification device address See the list of address ranges for the
PLC device type.
Usable devices (p.9-6)
Not set For cyclic data transfer
Completion notification bit
address
See the list of address ranges for the
PLC device type.
Usable devices (p.9-6)
Not set
Completion notification data
address
See the list of address ranges for the
PLC device type.
Usable devices (p.9-6)
Not set
Data settings
Transfer sheets 1 to 4 can be set independently. Up to 64 data items can be specified
in total for all sheets combined. The settings for each data item are shown in the
table below.
Item Settings Initial value Notes
PLC address See the list of address ranges for the
PLC device type.
Not set
C1M address Selectable from the C1M monitor data
and parameters.
Not set