5-4
Chapter 5. Functions
z
PV input range table (RTD)
C01
setting
Sensor type Range (Celsius)*
1
C04
display*
2
C04
setting
range
C04 initial
value*
3
41 Pt100 −200 to +500 °C - (Fixed) 0
42 JPt100 −200 to +500 °C - (Fixed) 0
43 Pt100 −200 to +200 °C - (Fixed) 0
44 JPt100 −200 to +200 °C - (Fixed) 0
45 Pt100 −100.0 to +300.0 °C
✓
0–1 0
46 JPt100 −100.0 to +300.0 °C
✓
0–1 0
51 Pt100 −50.0 to +200.0 °C
✓
0–1 1
52 JPt100 −50.0 to +200.0 °C
✓
0–1 1
53 Pt100 −50.0 to +100.0 °C
✓
0–1 1
54 JPt100 −50.0 to +100.0 °C
✓
0–1 1
63 Pt100 0.0 to 200.0 °C
✓
0–1 1
64 JPt100 0.0 to 200.0 °C
✓
0–1 1
67 Pt100 0.0 to 500.0 °C
✓
0–1 0
68 JPt100 0.0 to 500.0 °C
✓
0–1 0
*1. If the display range is exceeded, this device continues displaying the maximum or
minimum value that can be displayed.
*2. C04 is the setting of the decimal point position of the PV.
*3. C04 is reset to the initial value when C01 is changed.
C01
setting
Sensor type Range (Fahrenheit)*
1
C04
display*
2
C04
setting
range
C04 initial
value*
3
41 Pt100 −300 to +900 °F - (Fixed) 0
42 JPt100 −300 to +900 °F - (Fixed) 0
43 Pt100 −300 to +400 °F - (Fixed) 0
44 JPt100 −300 to +400 °F - (Fixed) 0
45 Pt100 −150 to +500 °F - (Fixed) 0
46 JPt100 −150 to +500 °F - (Fixed) 0
51 Pt100 −50.0 to +400.0 °F
✓
0–1 0
52 JPt100 −50.0 to +400.0 °F
✓
0–1 0
53 Pt100 −50.0 to +200.0 °F
✓
0–1 0
54 JPt100 −50.0 to +200.0 °F
✓
0–1 0
63 Pt100 0.0 to 400.0 °F
✓
0–1 0
64 JPt100 0.0 to 400.0 °F
✓
0–1 0
67 Pt100 0.0 to 900.0 °F
✓
0–1 0
68 JPt100 0.0 to 900.0 °F
✓
0–1 0
*1. If the display range is exceeded, this device continues displaying the maximum or
minimum value that can be displayed.
*2. C04 is the setting of the decimal point position of the PV.
*3. C04 is reset to the initial value when C01 is changed.