5-3
Chapter 5. Functions
C01
setting
Sensor type Range (Fahrenheit)*
1
C04
display*
2
C04
setting
range
C04 initial
value*
3
1 K −300 to +2200 °F - (Fixed) 0
2 K 0 to 2200 °F - (Fixed) 0
3 K 0 to 1500 °F - (Fixed) 0
4 K 0 to 1100 °F - (Fixed) 0
5 K 0.0 to 700.0 °F
✓
0–1 0
6 K −300 to +700 °F - (Fixed) 0
9 J 0 to 1500 °F - (Fixed) 0
10 J 0 to 1100 °F - (Fixed) 0
11 J −300 to +700 °F - (Fixed) 0
13 E 0 to 1100 °F - (Fixed) 0
14 T −300 to +700 °F - (Fixed) 0
15 R*
4
0 to 3000 °F - (Fixed) 0
16 S*
4
0 to 3000 °F - (Fixed) 0
17 B*
5
0 to 3300 °F - (Fixed) 0
18 N 0 to 2300 °F - (Fixed) 0
19 PLII 0 to 2300 °F - (Fixed) 0
20 WRe5-26 0 to 2400 °F - (Fixed) 0
21 WRe5-26 0 to 4200 °F - (Fixed) 0
23 PR40-20*
6
0 to 3400 °F - (Fixed) 0
24 DIN U −300 to +700 °F - (Fixed) 0
25 DIN L −150 to +1500 °F - (Fixed) 0
*1. If the display range is exceeded, this device continues displaying the maximum or
minimum value that can be displayed.
*2. C04 is the setting of the decimal point position of the PV.
*3. C04 is reset to the initial value when C01 is changed.
*4. Accuracy Below 200 °C: ±9 °C
*5. Accuracy Below 260 °C: ±80 °C (reference value), 260 °C to below 600 °C: ±12 ° C, 600 °C to
below 1000 °C: ±6 °C, 1000 °C or more: ±4.5 °C. Temperatures below 20 °C are not displayed.
*6. Accuracy Below 400 °C: not specified, 400 °C to below 1100 °C: ±40 °C, 1100 °C or more:
±12°C.