5-30
Chapter 5. Functions
Handling Precautions
Before starting AT, check that the PV input and the actuators (heater power,
etc.) are ready for control.
If CtrL (control method) is set to 0 (ON/OFF control), AT cannot start. Change
the control method setting to 1 (PID control).
Conditions for starting AT:
The device is in RUN and AUTO modes.
No PV input error has occurred.
The setting for “MV switching point PV in AT” is within the PV input range.
AT (automatic tuning) (p.5-24) (for Type of MV switching point at AT”)
PV input range type (p.5-2) (for the PV input range)
If any of the following is detected during AT, AT will stop without changing the
PID constants:
Switch to READY mode
Switch to MANUAL mode
PV error
Change in the setting of control method, “heat/cool control, control
operation (only when “heat/cool control” is set to 0 (not used)), sampling
cycle, and control algorithm
Change in the setting of “MV low limit” (OL-1 to 8), “MV low limit at AT” (At.OL),
“MV high limit” (OH-1 to 8), or “MV high limit at AT” (At.OH) that would prevent
change in the two-value output during AT
For forcible termination of AT by At (AT stop/start selection) in the mode bank
or by the internal contacts to which the function to stop/start AT is assigned,
see the section below:
5 - 7 Digital Input (DI) / Internal Contacts (p.5-47)
If AT is forced to stop, At.Er (auto tuning error) is set to Er.On (abnormal). At.Er
(auto tuning error) can be reset to Er.OF (normal)) by any of the following
operations.
Change the setting of At.Er (auto tuning error) to Er.OF (normal).
Try executing AT again until it ends normally.
Turn the power off and then back on.
If C26 (heat/cool control) is set to 2 (use (shared PID)), specify AT MV low limit
(at.ol) / AT MV high limit (at.oh) and MV low limit (ol-1 to 8) / MV high limit
(oh-1 to 8) so that both values that are output to the MV are 50 % or more.
If C26 (heat/cool control) is set to 1 (use (individual PID)),
The MV is limited by “MV low limit at AT (At.OL) / “MV high limit at AT (At.OH).
The heating MV is limited by “MV low limit” (OL-1 to 8) / “MV high limit (OH-1
to 8) for the PID constants.
The cooling MV is limited by cool-side MV low limit” (OL.1C to 8C) / “cool-side
MV high limit” (OH.1C to 8C).