S600+ Instruction Manual
Revised July-2017 Chromatographs C-15
Stage
Description
2
Wait for Status or Pre-
Analysis Reply
Wait up to the time-out period for the unit
to respond and then (depending on the
data being polled for) either:
Process the staus report checcking
for any critical alarms, if any alarms
are found then raise the alarms. Set
the next stage to Idle so that the
next poll requests the analysis data.
Check the returned message for the
values of the analysis flags and
calibration flags. If either of these
has changed value from the previous
pre analysis poll, then issue a new
poll to request the mole data and set
the next stage to Poll for Mole
Percentages. If the flags have not
changed in value then set the next
stage to Idle.
If the poll response indicated a failure
then set the next stage to Idle.
3
Poll for Mole Percentages
Wait up to the time-out period for the unit
to respond and then (depending on the
data being polled for) either:
If calibration data has been returned
then do not process this. Set the
next stage to Idle.
If this is analysis data then set the
next stage to Process Data.
If the poll response indicated a failure
then set the next stage to Idle.