3−28
Frequency-related Functions
Frequency Limits – Upper and lower
limits can be imposed on the inverter
output frequency. These limits will
apply regardless of the source of the
speed reference. You can configure the
lower frequency limit to be greater than
zero as shown in the graph. The upper
limit must not exceed the rating of the
motor or capability of the machinery.
The maximum frequency setting
(A004/A204) takes precedence over
frequency upper limit (A061/A261).
“A” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
A061
Frequency upper limit Sets a limit on output frequency
less than the maximum frequency
(A004).
Range is from frequency lower
limit (A062) to maximum
frequency (A004).
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
less than the maximum frequency
(A204).
Range is from frequency lower
limit (A262) to maximum
frequency (A204).
0.0 setting is disabled
>0.0 setting is enabled
U
0.00 Hz
A261
Frequency upper limit,
2nd motor
U
0.00 Hz
A062
Frequency lower limit Sets a limit on output frequency
greater than zero.
Range is start frequency (B082) to
frequency upper limit (A061)
0.0 setting is disabled
>0.0 setting is enabled
Sets a limit on output frequency
greater than zero.
Range is start frequency (B082) to
frequency upper limit (A261)
0.0 setting is disabled
>0.0 setting is enabled
U
0.00 Hz
A262
Frequency lower limit,
2nd motor
U
0.00 Hz
Output
frequency
A061