EasyManua.ls Logo

Hitachi WJ200 Series

Hitachi WJ200 Series
420 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
357
Display related parameters
Function code display restriction: b037 The function code display restriction allows
you to arbitrarily switch the display mode or the display content on the integrated
operator.
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
b037
Function code display
restriction
Seven option codes:
00Full display
01Function-specific display
02User setting (and b037)
03Data comparison display
04Basic display
05Monitor display only
U
04
(1) Function-specific display mode (b037=01)
If a specific function has not been selected, the monitor does not show the
parameters concerning the specific function. Following table lists the details of
display conditions.
No. Displayed conditions Displayed func. codes when condition fulfilled.
1 2nd motor C001...C007=08
F202, F203, A201 to A204, A220, A244, A245,
A261, A262, A281, A282, A292 to A296, b212,
b213, b221 to b223, C241, H202 to H204, H206
2 EzSQ A017=01,02 d023 to d027, P100 to P131
3 Sensorless vector control A044=03
d009, d010, d012, b040 to b046, C054 to C059,
H001, H005, H020 to H024, H030 to H034, P033,
P034, P036 to P040
4
Sensorless vector control
for 2nd motor
C001...C007=08
AND A244=03
d009, d010, d012, b040 to b046, C054 to C059,
H001, H205, H220 to H224, H230 to H234, P033,
P034, P036 to P040
5 Free V/F control
A044=02 OR
C001...C007=08 AND
A244=02
b100 to b113
6
Free setting of
electronic-thermal
b013=02 OR
C001...C007=08 AND
b213=02
b015 to b020
7 VC or VP
1.7
control A044=00,01 A041 to A043,A046, A047
8
VC or VP
1.7
control for 2nd
motor
C001...C007=08 AND
A244=00,01
A241 to A243, A246, A247
9 DC breaking
A051=01,02 OR
C001...C007=07
A052 to A059
10 PID A071=01,02
d004, A072 to A079, A156, A157, C044, C052,
C053
11 EzCOM C096=01,02 C098 to C100, P140 to P155
12 Curving accel/deceleration A097,A098=01...04 A131, A132, A150 to A153
13 Controlled deceleration b050=01,02,03 b051 to b054
14 Breaking b120=01 b121 to b127
15 Decel. overvolt. suppress b130=01,02 b131 to b134
16 Simple positioning P003=01
d008, P004, P011, P012, P015, P026, P027,
P060to P073, P075, P077, H050, H051

Table of Contents

Other manuals for Hitachi WJ200 Series