6−13
Trip History and Inverter Status
We recommend that you first find the cause of the fault before clearing it. When a fault
occurs, the inverter stores important performance data at the moment of the fault. To
access the data, use the monitor function (dxxx) and select d081 details about the
present fault. The previous 5 faults are stored in d082 to d086. Each error shifts
d081-d085 to d082-d086, and writes the new error to d081.
The following Monitor Menu map shows how to access the error codes. When fault(s)
exist, you can review their details by first selecting the proper function: D081 is the
most recent, and D086 is the oldest.
E072
Overload restriction
Note: Indicated inverter status could be
different from actual inverter behavior.
e.g. When PID operation or frequency given
by analog signal, although it seems constant
speed, acceleration and deceleration could
be repeated in very short cycle.