384
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
C011
Input [1] active state Select logic conversion, two option
codes:
00normally open [NO]
01normally closed [NC]
U
00
C012
Input [2] active state
U
00
C013
Input [3] active state
U
00
C014
Input [4] active state
U
00
C015
Input [5] active state
U
00
C016
Input [6] active state
U
00
C017
Input [7] active state
U
00
NOTE: An input terminal configured for option code 18 ([RS] Reset command) cannot be
configured for normally closed operation.
Note: This response time is disregarded when power-on or reset. For example, when the
power is up when FW terminal is on, then the operation starts regardless this response
time as soon as the internal reset process is completed.
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
C160
Input [1] response time Sets response time of each input
terminal, set range:
0 (x 2 [ms]) to 200 (x 2 [ms])
(0 to 400 [ms])
U
1.
C161
Input [2] response time
U
1.
C162
Input [3] response time
U
1.
C163
Input [4] response time
U
1.
C164
Input [5] response time
U
1.
C165
Input [6] response time
U
1.
C166
Input [7] response time
U
1.
Intelligent Input Terminal Overview
Each of the seven intelligent terminals may be assigned any of the options in the
following table. When you program one of the option codes for terminal assignments
C001 to C007, the respective terminal assumes the function role of that option code. The
terminal functions have a symbol or abbreviation that we use to label a terminal using
that function. For example, the “Forward Run” command is [FW]. The physical label on
the terminal block connector is simply 1, 2, 3, 4, 5, 6, or 7. However, schematic examples
in this manual also use the terminal symbol (such as [FW]) to show the assigned option.
The option codes for C011 to C017 determines the active state of the logical input (active
high or active low).