C−25
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
C147
Logic output 2 operator Applies a logic function to calculate
[LOG] output state,
Three options:
00…[LOG] = A AND B
01…[LOG] = A OR B
02…[LOG] = A XOR B
U
00
−
C148
Logic output 3 operand A
All the programmable functions
available for logic (discrete) outputs
except LOG1 to LOG3, OPO, no
U
00
−
C149
Logic output 3 operand B
U
01
−
C150
Logic output 3 operator Applies a logic function to calculate
[LOG] output state,
Three options:
00…[LOG] = A AND B
01…[LOG] = A OR B
02…[LOG] = A XOR B
U
00
−
C160
Input [1] response time Sets response time of each input
terminal, set range:
0 (x 2 [ms]) to 200 (x 2 [ms])
(0 to 400 [ms])
U
1.
−
C161
Input [2] response time
U
1.
−
C162
Input [3] response time
U
1.
−
C163
Input [4] response time
U
1.
−
C164
Input [5] response time
U
1.
−
C165
Input [6] response time
U
1.
−
C166
Input [7] response time
U
1.
−
C169
Multistage speed/position
determination time
Set range is 0. to 200. (x 10ms)
U
0. ms
Motor Constants Functions
“H” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description
Lnitial
data
Units
H001
Auto-tuning selection Three option codes:
00…Disabled
01…Enabled with motor stop
02…Enabled with motor rotation
U
00 -
H002
Motor constant selection Four option codes:
00…Hitachi standard motor
02…Auto tuned data
U
00 -
H202
Motor constant selection,
2
nd
motor
U
00 -
H003
Motor capacity Eleven selections:
0.1/0.2/0.4/0.75/1.5/2.2/3.7/
5.5/7.5/11/15/18.5
U
Specified by
the capacity
of each
inverter
model
kW
H203
Motor capacity,
2
nd
motor
U
kW
H004
Motor poles setting Four selections:
2 / 4 / 6 / 8 / 10
U
4 poles
H204
Motor poles setting,
2
nd
motor
U
4 poles