4−54
Run Signal
When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when it is
in Run Mode. The output logic is active low,
and is the open collector type (switch to
ground).
Option
Code
Terminal
Symbol
Function Name State Description
00
RUN Run Signal ON when inverter is in Run Mode
OFF when inverter is in Stop Mode
alid for inputs:
11, 12, AL0 – AL2 Example for terminal [11] (default output
configuration shown – see page 3-90):
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see page 4-52 and 3-90):
See I/O specs on page 4-6
Required settings
(none)
Notes:
• The inverter outputs the [RUN] signal whenever
the inverter output exceeds the start frequency
specified by parameter B082. The start frequency
is the initial inverter output frequency when it turns
ON.
• The example circuit for terminal [11] drives a relay
coil. Note the use of a diode to prevent the
negative going turn-off spike generated by the coil
from damaging the inverter’s output transistor.
RY
Inverter output
terminal circuit
CM2 11
RUN
AL1
Power
supply
Load
AL0 AL2
Inverter logic
circuit board
RUN
[FW,RV]
1
0
Output
frequency
t
Run
signal
1
0
start freq.
B082