353
Software Lock Mode
The software lock function keeps personnel from accidentally changing parameters in
the inverter memory. Use B031 to select from various protection levels.
The table below lists all combinations of B031 option codes and the
ON/OFF state of the [SFT] input. Each Check
or Ex U indicates
whether the corresponding parameter(s) can be edited. The
Standard Parameters column below shows access in permitted for
some lock modes. These refer to the parameter tables throughout
this chapter, each of which includes a column titled
Run Mode Edit
as shown to the right.
The marks (Check
or Ex U) under the “Run Mode Edit” column title indicate
whether access applies to each parameter as defined in the table below. In some lock
modes, you can edit only F001 and the Multi-speed parameter group that includes A020,
A220, A021A035, and A038 (Jog). However, it does not include A019, Multi-speed
operation selection. The editing access to B031 itself is unique, and is specified in the
right-most two columns below.
B031
Lock
Mode
[SFT]
Intelligent
Input
Standard Parameters
F001 and
Multi-Speed
B031
Stop Run Stop and Run Stop Run
00
OFF
Run mode
edit access
U
ON
U U U
U
01
OFF
Run mode
edit access
U
ON
U U
U
02
(ignored)
U U U
U
03
(ignored)
U U
U
10
(ignored)
High level
access
NOTE: Since the software lock function B031 is always accessible, this feature is not the
same as password protection used in other industrial control devices. So if you want to
use password function, use parameter B037 together with the B031. See section 4-104 for
detailed explanation of the password function.
Run
Mode
Edit
U