3−56
Reduced voltage start
The reduced voltage start function enables you to make the inverter increase the output
voltage gradually when starting the motor.
Set a small value for the reduced voltage start selection (b036) if you intend to increase
the start torque. On the other hand, setting a small value will cause the inverter to
perform full-voltage starting and to easily trip because of overcurrent.
“b” Function
Run
Mode
Edit
Defaults
Func.
Code
Name Description Lnitial data Units
b036
Reduced voltage start
selection
Set range, 0 (disabling the function), 1
(approx. 6ms) to 255 (approx. 1.5s)
U
2
−
FW
Start freq. b082
Output freq.
Reduced voltage start
b036
Output voltage
00 06 01