Output Function Summary Table This table shows all functions for the logical outputs
(terminals [11], [12] and [AL]) at a glance. Detailed descriptions of these functions,
related parameters and settings, and example wiring diagrams are in “Using Intelligent
Output Terminals” in chapter 4.
Output Function Summary Table
Option
Code
Terminal
Symbol
Function Name Description
00
RUN Run Signal ON When the inverter is in Run Mode
OFF When the inverter is in Stop Mode
01
FA1 Frequency Arrival Type
1–Constant Speed
ON When output to motor is at the set frequency
OFF When output to motor is OFF, or in any acceleration
or deceleration ramp
02
FA2 Frequency Arrival Type
2–Over frequency
ON When output to motor is at or above the set freq.,
even if in accel (C042) or decel (C043) ramps
OFF When output to motor is OFF, or at a level below the
set frequency
03
OL Overload Advance
Notice Signal 1
ON When output current is more than the set threshold
(C041) for the overload signal
OFF When output current is less than the set threshold
for the deviation signal
04
OD Output Deviation for PID
Control
ON When PID error is more than the set threshold for
the deviation signal
OFF When PID error is less than the set threshold for the
deviation signal
05
AL Alarm Signal ON When an alarm signal has occurred and has not
been cleared
OFF When no alarm has occurred since the last cleaning
of alarm(s)
06
FA3 Frequency Arrival Type
3–Set frequency
ON When output to motor is at the set frequency, during
accel (C042) and decel (C043).
OFF When output to motor is OFF, or is not at a level of
the set frequency
07
OTQ Over/under Torque
Signal
ON Estimated motor torque exceeds the specified level
OFF Estimated motor torque is lower than the specified
level
09
UV Undervoltage ON Inverter is in Undervoltage
OFF Inverter is not in Undervoltage
10
TRQ Torque Limited Signal ON Torque limit function is executing
OFF Torque limit function is not executing
11
RNT Run Time Expired ON Total running time of the inverter exceeds the
specified value
OFF Total running time of the inverter does not exceed
the specified value
12
ONT Power ON time Expired ON Total power ON time of the inverter exceeds the
specified value
OFF Total power ON time of the inverter does not exceed
the specified value
13
THM Thermal Warning ON
Accumulated thermal count exceeds the C061 set
value
OFF Accumulated thermal count does not exceed the
C061 set value
19
BRK Brake Release Signal ON Output for brake release
OFF No action for brake
20
BER Brake Error Signal ON Brake error has occurred
OFF Brake performance is normal
21
ZS Zero Hz Speed
Detection Signal
ON Output frequency falls below the threshold specified
in C063